Use a thermostat with all lube oil heaters to protect the oil from overheating. Lube oil heaters must always be installed in the sump with the entire heater submerged below the oil level at all times.
Lube Oil Heater (Weathertight)
د.إ0.000
Temperature Range | Code | |
ON | OFF | |
60°F (16C) | 80°F (27C) | 6 |
80°F (27C) | 100°F(38C) | 8 |
100°F(38C) | 120°F (49C) | 10 |
Power (Heater) | 50 Watts, 75 Watts, 125 Watts, 150 Watts, 225 Watts, 300 Watts, 450 Watts, 500 Watts |
---|---|
Oil Heater | |
Product Type | Genset |
QR Code
Related Products
- desktop-columns-3 tablet-columns-2 mobile-columns-1
-
SB Model
د.إ0.000Availability: In stockOut of stock
3 Range Model:
Fixed Thermostat:
80–100 °F (24–38°C)
100–120 °F (38–49 °C)
120–140 °F (49–60 °C)Adjustable 90° – 130°F (32°C – 54°C)
-
CMM Model
د.إ0.000Availability: In stockOut of stock
- Heating Fluid: Engine coolant (50% glycol/50% water)
- Power: 12 – 24kW
- Rated Voltage: 400V/50Hz/3ph, 440V/60Hz/3ph, 690V/50&60Hz/3ph
- Temperature Controller: Adjustable 32°-212°F (0°-100°C)
- Temperature Setting: 120°F (50°C)
- High Limit Temperature Control: Adj. 32°-212°F (0°-100°C)
- High Limit Temperature Setting: 195°F (90°C)
- Fluid Capacity: 0.8 gal (3.0L)
- Pump Power: 0.5Hp (0.37kW)
-
AF27993NF Air Filter
د.إ0.000Availability: In stockOut of stock
Features:
■ Nanofibre filter media provides the highest possible engine protection efficiency without compromising filter life
■ Pleat geometry, spacing and stabilization yields maximum filter performance and long life for lower equipment operating costs
■ Proven radial air filter seal ensures reliable fit in the SSG air housing and easy service events
■ Complete Fleetguard system solution including the AF27994 secondary filter and the SP1307 housing service cover -
DLV System
د.إ0.000Availability: In stockOut of stock
Specification:
Heating Fluid: Coolant and Oil
Coolant Heat Power: 18 – 30 kW
Oil Heat Power: 6 – 12 kW
Rated Voltage: 208, 240, 480, 575 V (3Ø 60 Hz)
220, 380, 400, 415 V (3Ø 50 Hz)
Temp Controller, coolant: Adj. 32 – 212 °F (0 – 100 °C), preset from factory at 122 °F (50 °C)
Temp Controller, oil: Adj. 32 – 212 °F (0 – 100 °C), preset from factory at 104 °F (40 °C)
High-Limit Temperature Protection
Main Control Box Ingress Protection: NEMA 4 IP66
Coolant Motor Ingress Protection: IP55
Oil Motor Ingress Protection: IP55
Meets Vibration Specification IEC 60068-2-64
Meets Shock Specification IEC 60068-2-27 -
CSM Style A
د.إ0.000Availability: In stockOut of stock
HOTflow™ model CSM was developed to preheat diesel and gas engines for stationary land power, marine, large mining and construction equipment.
-
-
WL Model
د.إ0.000Availability: In stockOut of stock
HOTSTART tank style engine heaters were developed to pre-heat diesel and gas engines for stationary land power, heavy duty mobile equipment, marine and offshore equipment.
-
CLM Model
د.إ0.000Availability: In stockOut of stock
-
Heating Fluid: Engine coolant (50% glycol/50% water
Power: 27-36kW
Rated Voltage: 400V/50Hz/3ph, 440V/60Hz/3ph, 690V/50&60Hz/3ph
Temperature Controller: Adjustable 32°-212°F (0°-100°C)
Temperature Setting: 120°F (50°C)
High Limit Temperature Control: Adj. 32°-212°F (0°-100°C)
High Limit Temperature Setting: 195°F (90°C)
Fluid Capacity: 0.9 gal (3.5L)
Pump Power: 0.75Hp (0.55kW)
-
-
CL Model
د.إ0.000Availability: In stockOut of stock
3 Range Model:
- Fixed Thermostat:
80–100 °F (24–38°C)
100–120 °F (38–49 °C)
120–140 °F (49–60 °C)
- Adjustable 90° – 130° (32°C – 54°C)
- Fixed Thermostat:
Reviews