Use a thermostat with all lube oil heaters to protect the oil from overheating. Lube oil heaters must always be installed in the sump with the entire heater submerged below the oil level at all times.
Lube Oil Heater (Weathertight)
د.إ0.000
Temperature Range | Code | |
ON | OFF | |
60°F (16C) | 80°F (27C) | 6 |
80°F (27C) | 100°F(38C) | 8 |
100°F(38C) | 120°F (49C) | 10 |
Power (Heater) | 50 Watts, 75 Watts, 125 Watts, 150 Watts, 225 Watts, 300 Watts, 450 Watts, 500 Watts |
---|---|
Oil Heater | |
Product Type | Genset |
QR Code

Related Products
-
OCSM Model
د.إ0.000Availability: In stockOut of stock
- Primary Heating Fluid: Engine Coolant
- Secondary Heating Fluid: Engine Oil
- Heat Power: 6, 9, 12 kW
- Voltage Range: 1 or 3 Phase 208 – 600V (50 or 60 Hz)
- Temperature Controller: Fixed 100 – 120 °F (38 – 49 °C)
- High-Limit Temp. Control: Fixed 165 – 205 °F (74 – 96 °C)
- Fluid Capacity: Coolant – 0.7 gal (2.6L)
- Oil – 0.2 gal (0.8L)
- Pump Power: Coolant – 0.04 Hp (0.03 kW)
- Oil – 0.33 Hp (0.25 kW)
-
CMM Model
د.إ0.000Availability: In stockOut of stock
- Heating Fluid: Engine coolant (50% glycol/50% water)
- Power: 12 – 24kW
- Rated Voltage: 400V/50Hz/3ph, 440V/60Hz/3ph, 690V/50&60Hz/3ph
- Temperature Controller: Adjustable 32°-212°F (0°-100°C)
- Temperature Setting: 120°F (50°C)
- High Limit Temperature Control: Adj. 32°-212°F (0°-100°C)
- High Limit Temperature Setting: 195°F (90°C)
- Fluid Capacity: 0.8 gal (3.0L)
- Pump Power: 0.5Hp (0.37kW)
-
CSM Style A
د.إ0.000Availability: In stockOut of stock
HOTflow™ model CSM was developed to preheat diesel and gas engines for stationary land power, marine, large mining and construction equipment.
-
OSE Model
د.إ0.000Availability: In stockOut of stock
Heating Fluid: Oil
Heat Power: 1.5, 2.5 kW
Voltage Range: 480V/60Hz/3ph (Contact HOTSTART for other voltage requirements)
Temperature Controller: Adjustable 32°-212°F (0°-100°C)
Temperature Setting: 105°F (40°C)
High-Limit Temperature Control: Adj. 32°-212°F (0°-100°C)
High-Limit Temperature Setting: 195°F (90°C)
Fluid Capacity: 0.6 gal (2.2L)
Pump Power: 0.75, 2Hp (0.56, 1.5 kW) -
SL Model
د.إ0.000Availability: In stockOut of stock
3 Range Model:
Fixed Thermostat:
80–100 °F (24–38°C)
100–120 °F (38–49 °C)
120–140 °F (49–60 °C)
Adjustable 90° – 130°F (32°C – 54°C)
-
OCLE Model
د.إ0.000Availability: In stockOut of stock
Heating Fluid: Oil/Coolant
Heat Power: Oil 2.5 – 12 kW / Coolant 6 – 36 kW
Voltage Range: 208, 240, 440 – 480, 575 – 600 V
Temperature Controller: Adjustable 32 – 212 °F (0 – 100 °C)
Temperature Setting: Oil 105 °F (40 °C) / Coolant 120 °F (50 °C)
High-Limit Temperature Control: Adjustable 32–212 °F (0 – 100 °C)
High-Limit Temperature Setting: 195 °F (90 °C)
Fluid Capacity: 1 gal (3.8 L)
Pump Power: Oil 1 – 3 Hp (0.75 – 2.25 kW) Coolant 1 Hp (0.75 kW)
Maximum Pressure: 100 psi (690 kPa) -
Silicone Hot Pad
د.إ0.000Availability: In stockOut of stock
Easy peel and stick application
Etched foil heating element for optimal heat transfer and long life.
Durable silicone/fiberglass cover resists abrasion.
120 V models are assembled with a standard 6’ (1.8m) HPN cord and plug.
240 V models include 6’ (1.8m) HPN cord without plug. -
SB Model
د.إ0.000Availability: In stockOut of stock
3 Range Model:
Fixed Thermostat:
80–100 °F (24–38°C)
100–120 °F (38–49 °C)
120–140 °F (49–60 °C)Adjustable 90° – 130°F (32°C – 54°C)
-
OCLA System
د.إ0.000Availability: In stockOut of stock
SPECIFICATIONS
Heating Fluid: Oil/Coolant
Heat Power: Oil 2.5 – 12 kW / Coolant 6 – 36 kW
Voltage Range: 230, 400 V
Temperature Controller: Adjustable 0 – 100 °C (32 – 212 °F)
Temperature Setting: Oil 40 °C (105 °F) / Coolant 50 °C (120 °F)
High-Limit Temperature Control: Adjustable 0 – 100 °C (32 – 212°F)
High-Limit Temperature Setting: 90 °C (195 °F)
Fluid Capacity: 3.8 L (1 gal)
Pump Power: Oil 0.75 – 2.25 kW (1 – 3 Hp)
Coolant 0.75 kW (1 Hp)