The HOTSTART DLV is a complete, packaged dual heating system with PT-100 temperature sensors, pump, motor and all required controls. It heats and circulates coolant and lube oil throughout the entire engine and cooling system. This system heats engines up to 300 L displacement. Forced circulation of the fluid delivers uniform heating throughout the entire engine, enhances equipment availability and decreases wear and tear from cold starts.
DLV System
د.إ0.000
Specification:
Heating Fluid: Coolant and Oil
Coolant Heat Power: 18 – 30 kW
Oil Heat Power: 6 – 12 kW
Rated Voltage: 208, 240, 480, 575 V (3Ø 60 Hz)
220, 380, 400, 415 V (3Ø 50 Hz)
Temp Controller, coolant: Adj. 32 – 212 °F (0 – 100 °C), preset from factory at 122 °F (50 °C)
Temp Controller, oil: Adj. 32 – 212 °F (0 – 100 °C), preset from factory at 104 °F (40 °C)
High-Limit Temperature Protection
Main Control Box Ingress Protection: NEMA 4 IP66
Coolant Motor Ingress Protection: IP55
Oil Motor Ingress Protection: IP55
Meets Vibration Specification IEC 60068-2-64
Meets Shock Specification IEC 60068-2-27
Product Type | Genset |
---|---|
Power (Heater) | |
Combined Coolant & Oil Heater | Coolant/Lube Oil Heating System |
Power (Oil Heater) | 12 KW, 6 KW, 9 KW |
QR Code
Related Products
-
TPS Model
د.إ0.000Availability: In stockOut of stock
- Application:
The TPS engine pre-heater is designed to pre-heat diesel and gas engines in genset, heavy duty mobile equipment, marine and industrial applications.
3 Range Model:
Fixed Thermostat:
80–100 °F (24–38°C)
100–120 °F (38–49 °C)
120–140 °F (49–60 °C)Adjustable Thermostat 90–130 °F (32–54 °C)
Voltage Range: 120 and 240 V -
Lube Oil Heater (Weathertight)
د.إ0.000Availability: In stockOut of stock
Temperature Range Code ON OFF 60°F (16C) 80°F (27C) 6 80°F (27C) 100°F(38C) 8 100°F(38C) 120°F (49C) 10 -
CB Model
د.إ0.000Availability: In stockOut of stock
3 Range Model:
- Fixed Thermostat:
80–100 °F (24–38°C)
100–120 °F (38–49 °C)
120–140 °F (49–60 °C)
-
Immersion Heater
د.إ0.000Availability: In stockOut of stock
TEMPERATURE RANGE CONTROL ON OFF 60°F (16C) 80°F (27C) HLC-6 80°F (27C) 100°F (38C) HLC-8 100°F (38C) 120°F (49C) HLC-10 ELECTRICAL RATING 15 Amps at 120 Vac 10 Amps at 240 Vac 10 Amps at 277 Vac -
SL Model
د.إ0.000Availability: In stockOut of stock
3 Range Model:
Fixed Thermostat:
80–100 °F (24–38°C)
100–120 °F (38–49 °C)
120–140 °F (49–60 °C)
Adjustable 90° – 130°F (32°C – 54°C)
-
OSM Model
د.إ0.000Availability: In stockOut of stock
Primary Heating Fluid: Engine Oil
Heat Power: 1, 2, 3 kW
Voltage Range: 1 or 3 Phase 120-690V (50 or 60Hz)
Temperature Controller: Fixed 80°-100°F (27°-38°C)
High-Limit Temp. Control: Fixed 165°-205°F (74°-96°C)
Fluid Capacity: Oil – 0.6 gal (2.2L)
Pump Power: 0.33 Hp (.25 kW) -
CL Model (Watertight)
د.إ0.000Availability: In stockOut of stock
Pressure switch or relay for automatic operation
Universal mounting for varied mounting configuration
100° to 120°F fixed thermostats
On/Off switch for manual control
Watertight components rated NEMA 12
Viton mechanical seal pumps for extended seal life and temperatures to 350°F
External motor protective switch reset button -
OCLA System
د.إ0.000Availability: In stockOut of stock
SPECIFICATIONS
Heating Fluid: Oil/Coolant
Heat Power: Oil 2.5 – 12 kW / Coolant 6 – 36 kW
Voltage Range: 230, 400 V
Temperature Controller: Adjustable 0 – 100 °C (32 – 212 °F)
Temperature Setting: Oil 40 °C (105 °F) / Coolant 50 °C (120 °F)
High-Limit Temperature Control: Adjustable 0 – 100 °C (32 – 212°F)
High-Limit Temperature Setting: 90 °C (195 °F)
Fluid Capacity: 3.8 L (1 gal)
Pump Power: Oil 0.75 – 2.25 kW (1 – 3 Hp)
Coolant 0.75 kW (1 Hp) -
WF 2073 Water Filter
د.إ0.000Availability: In stockOut of stock
WF2073
Media Type: Cellulose 60 23
Micron Rating: 60
Coolant Additive: 23 Units
Overall Height inch (mm): 5.43 (137.92)
Thread Size: 11/16-16 UN- 2B